【Scope of application】
This test furnace is developed according to the technical indicators and requirements stipulated in the national standard GB/T5464-2010, and is suitable for the test method for evaluating the combustion performance of building materials under laboratory conditions. It is suitable for testing the combustion performance classification of Class A fireproof materials in the GB8624 combustion performance classification of building materials
【Relevant Standards】
GB/T5464-2010 GB/T8624 ISO1182 Fire reaction test — non-flammable test of construction products
【Scope of application】:
This test furnace is developed according to the technical indicators and requirements stipulated in the national standard GB/T5464-2010, and is suitable for specifying the test method for evaluating the combustion performance of building materials under laboratory conditions. It is suitable for testing the combustion performance classification of A-class fireproof materials in the combustion performance classification of building materials GB8624
【Compliance with standards】
GB/T5464-2010 GB/T8624 ISO1182 Fire reaction test — non-flammable test of construction products
[Instrument features]:
1. Dual control mode: the operation can be controlled on the touch screen, or it can be controlled on the computer, and the operation mode can be easily switched; one device can be operated by several computers at the same time, and several computers can be online at the same time, which can realize LAN sharing; (users bring their own computers and printers; the host computer software, router, network cable will be sent with the device)
2. With automatic stakeout function, the sample can be automatically put into the furnace chamber after the temperature is stable, and the specimen basket will automatically rotate 90 degrees after the furnace outlet, when changing the sample. The automatic stakeout process can be stopped at any time, and the specimen basket can be automatically returned to the initial position;
3. Microcomputer technology and triac technology are used to adjust the temperature of the furnace body through power
4. High degree of automation, the temperature in the furnace, the specimen center, and the specimen surface temperature are displayed and recorded during the test, and the operation prompt will automatically pop out for the test step
5. Historical curves can be queried to automatically judge temperature balance
6. The testing process is safe, reliable and easy to operate
7. Customized version of mold molded refractory furnace, good thermal insulation performance
8. With high-quality bar heaters, the furnace temperature can be raised to 900 °C
9. PLC+NAbview professional software displays the temperature inside the furnace, the center temperature of the specimen and the temperature curve of the specimen surface in real time, which can realize automatic control, data acquisition and processing, data storage and output of measurement results.
10. The top is equipped with an observation mirror, which is convenient for users to safely observe the combustion status of the specimen in the furnace.
【Technical Parameters】
1. Furnace specifications: Φ40cm and height 1.5m.
2. 80/20 nickel-chromium resistance strip specification: 0.2mm thick, 3mm wide.
3. Automatic sample loading device: length 8cm, width 8cm, height 83cm.
4. The specimen basket travels 2cm wide and 38cm long.
5. The elongation range of the viewing lens is 0-30cm.
6. Specimen specification: Φ45×50 (mm).
7. The inner diameter of the heating furnace tube is 75mm±1mm, the outer diameter is Φ90mm±1mm, the height is 150mm±1mm, and the power is about 2KW
8. Thermocouple: nickel-chromium-nickel-silicon armored thermocouple, outer diameter is 1.5mm, wire diameter is 0.3mm, heating wire power: 2KW
9. Temperature stability time in the furnace: from room temperature to 750°C stable can be tested for about 1h
10. Place the thermocouple in the furnace, the thermocouple in the center of the specimen, and the thermocouple on the surface of the specimen;
11. 360-degree rotatable and liftable thermocouple scanning device;
12. Stainless steel inverted conical air regulator and cylindrical deflector;
13. The software automatically controls the heating rate and controls the furnace temperature in stages.
14. Usage environment: -5°C—40°C.
15. Power supply voltage: AC220V±10%, 50Hz, current ≤10A;
16. Stability time: from room temperature to 750°C≤1h;
17. The heating source is an electric furnace preheated to 750±5 degrees, the maximum temperature in the furnace is 900 degrees, the temperature in the furnace is 750±5°C, and the temperature drift does not exceed 2°C within 10 minutes
18. Temperature measurement accuracy: ≤±0.5°C.
19. Heating power: 800-1000W;
20. Maximum power: 1.5KW;
21. Power heating voltage: 0~100 V adjustable;
22. The software contains the current regression judgment temperature equilibrium conditions